EN: Installation Sheet
Introduction
The EV1000 series includes models EV1012 and EV1012AM.
These detectors have a patented mirror, pyro, and signal
processing technology.
Note: EV1012AM has not been evaluated by UL/cUL.
Installation guidelines
The technology used in these detectors resists false alarm
hazards. However, avoid potential causes of instability such as
(see Figure 1):
• Direct sunlight on the detector
• Strong draughts onto the detector
• Heat sources within the detector field of view
• Large animals within the detector field of view
• Obscuring the detector field of view with large objects,
such as furniture
• Objects within 50 cm (20 in.) of the anti-masking (AM)
detector
• Installing two detectors facing each other and less than
50 cm (20 in.) apart
Installing the detector
Figure 7 legend
Item Description
(1) Standard connection (factory default)
(2) Dual loop connection
CP Control panel
WT Walk test
AM Antimasking
D/N Day/night
Rtest Remote test
To install the detector:
1. Lift off the custom insert and remove the screw
(see Figure 2, item 1).
2. Using a screwdriver, carefully prise open the detector (see
Figure 2, items 2 and 3).
3. Fix the base to the wall between 1.8 m and 3.0 m (5.9 and
9.8 ft.) from the floor. For flat mounting use a minimum of
two screws (DIN 7998) in positions A. For corner-mounting
use screws in positions B or C (Figure 3). To install a pry-
off tamper, use position A or B.
Note: Using the pry-off tamper has not been evaluated by
UL/cUL.