21-3602E rev1.5 Monitor xL™ Advanced Installation Guide 13
S00500 Dialer Selections
Keypad Selections
(left to right on keypad screen) Example:
Default Name Selections Description
000000 Dialer
Account
Number
(Primary)
The system’s monitoring station receiver
number that will identify the premises.
1
Telco Modem
Type
1 = Bell 103, 2 = 8OP STU, 3 = WWMODEM
4 = WWMODEM 8OP STU
STU = Subscriber Terminal Unit
WW = World Wide
(UK ACPO = 2)
(European = 3)
0
Telco Alarm
Report Mode
0 = not used, 1 = primary, 2 = backup, 3 = dual
4 = future
NOTE: “0” turns dialer off and clears all
the messages in the buffer
0
Telco Format 0 = SIA Level 2, 1 = CID, 2 = SIA Level 3
(future), 3 = Future
0
Telco
Sequence
0: ULC
1: UL compatible
2: Long
3: MONITOR Standard
(in Canada use 0 or 3)
Call Sequence Details: (P = Primary phone
# attempt; B = Backup phone # attempt)
0 (ULC): PPBBPPBB / delay 60 min /
PPBBPPBB / delay 60 min / PPBBPPBB /
delay 60 min / PPBBPPBB.
1 (UL): PPBBPPBBPB / delay 10 min.
2 (Long): PPPPBBBB / delay 10 min /
PPPPBBBB / delay 30 min / PPPPBBBB /
delay 60 min / PPPPBBBB /
delay 2 hours / PPPPBBBB.
3 (MONITOR Standard): PPBP / delay 5
min / PPBP / delay 10 min / PPBP / delay
30 min / PPBP / delay 60 min / PPBP /
delay 2 hours / PPBP.
(no)
Telco –
prioritized
reporting
(yes) □ (no)
(yes)
Telco – never
allow blind
dialing
(yes) □ (no)
Dials regardless of detecting a dial
tone.
(UK ACPO = yes)
Telco = Telephone Company
S00501 Keypad Selections (left to right on keypad screen)
Default Name Selections Description
Blank
(16 characters)
Primary Phone Number
–
First Monitoring Station phone number the system will
dial to transmit reports.
The phone number can be preceded with P =pulse dialing (default), or T
=Tone dialing, and can include D =2 sec Delay, A =Star key (tone
dialing), # = Pound Sign (tone dialing), and/or W = Wait for second dial
tone. For T
one dialing, ensure the phone line supports this.
S00502 Keypad Selections (left to right on keypad screen)
Default Name Selections Description
Blank
(16 characters)
Secondary Phone
Number
–
Second Monitoring Station phone number the system will
dial to transmit reports, if dialing the primary phone
number is unsuccessful.
The phone number can be preceded with P =pulse dialing (default), or T
=Tone dialing, and can include D =2 sec Delay, A =Star key (tone
dialing), # = Pound Sign (tone dialing), and/or W = Wait for second dial
tone. For T
one dialing, ensure the phone line supports this.
000000·1·0·0·0
Save S00500